Every motor problem starts with the full-load current from the tables in Article 430, not from the nameplate. From that one number you size the conductors at 125% and the branch-circuit protective device at the percentage Table 430.52 gives for the type of device.

The method

  1. Find the full-load current in Table 430.248 for a single-phase motor or Table 430.250 for a three-phase motor.
  2. Branch-circuit conductors: at least 125% of that table current, under 430.22.
  3. Short-circuit and ground-fault protection: the table current times the percentage in Table 430.52 for the device, a fuse or a breaker.
  4. If the result is not a standard rating, 430.52 allows the next standard size up. The standard ratings are listed in 240.6(A).
  5. Overload protection is the one calculation that uses the nameplate current.

Two mistakes cost most of the points: reading the nameplate where the table is required, and using the conductor percentage for the protective device.

Worked problems

Problem 1. A 100 HP, 460-volt three-phase squirrel-cage motor is protected by a dual-element (time-delay) fuse. What is the maximum standard rating the Code permits for the branch-circuit short-circuit and ground-fault protective device?

Answer: 225 A

Table 430.250 gives 124 A full-load current. Table 430.52 permits up to 175% for a dual-element (time-delay) fuse: 124 x 1.75 = 217.0 A. Since that is not a standard rating, 430.52(C)(1) Exception No. 1 permits going up to the next standard size: 225 A. Do not confuse this with the conductor, sized at 125% = 155.0 A: they are two different calculations on the same motor.

Reference: NEC 430.52 and Table 430.250

Problem 2. A 60 HP, 230-volt three-phase squirrel-cage motor is protected by a dual-element (time-delay) fuse. What is the maximum standard rating the Code permits for the branch-circuit short-circuit and ground-fault protective device?

Answer: 300 A

Table 430.250 gives 154 A full-load current. Table 430.52 permits up to 175% for a dual-element (time-delay) fuse: 154 x 1.75 = 269.5 A. Since that is not a standard rating, 430.52(C)(1) Exception No. 1 permits going up to the next standard size: 300 A. Do not confuse this with the conductor, sized at 125% = 192.5 A: they are two different calculations on the same motor.

Reference: NEC 430.52 and Table 430.250

Problem 3. A 2 HP, 460-volt three-phase squirrel-cage motor is protected by a dual-element (time-delay) fuse. What is the maximum standard rating the Code permits for the branch-circuit short-circuit and ground-fault protective device?

Answer: 15 A

Table 430.250 gives 3.4 A full-load current. Table 430.52 permits up to 175% for a dual-element (time-delay) fuse: 3.4 x 1.75 = 6.0 A. Since that is not a standard rating, 430.52(C)(1) Exception No. 1 permits going up to the next standard size: 15 A. Do not confuse this with the conductor, sized at 125% = 4.2 A: they are two different calculations on the same motor.

Reference: NEC 430.52 and Table 430.250

Practice against the clock

Train on the full simulator

Full-length timed exams at the real format, unlimited practice with new numbers every time, drills on your weak subject areas, and study material: a four-week plan, exam-day strategy and the mistakes to avoid in each subject area.

Get full access$19 per month. Cancel any time.
First month refunded within 7 days.

Common questions

Do I use the nameplate current to size motor conductors?

No. Use the full-load current from Table 430.248 or Table 430.250 and size the conductors at 125% of it under 430.22. The nameplate current is for overload protection.

Can I round up the motor breaker size?

When the calculated value is not a standard rating, 430.52 permits the next higher standard size listed in 240.6(A).