Box fill calculations

A box fill problem is a count. Under 314.16(B) each item in the box is worth a number of volume allowances, each allowance is the volume the Code assigns to a conductor size, and the box must have at least the total.

What counts, and for how much

Find the volume for each conductor size in the table in 314.16(B), multiply, and add. The classic mistake is counting every grounding conductor separately.

Worked problems

Problem 1. Per 314.16(B), what minimum box volume in cubic inches is required for a box containing 11 current-carrying 12 AWG conductors passing through, 3 equipment grounding conductors, internal cable clamps, 1 device mounted on a yoke (receptacle or switch)?

Answer: 33.75 cu in

Look up the volume 314.16(B) assigns to 12 AWG in your Code book, then add each item: conductors: 11 x 2.25 = 24.75; clamps, all counted as one: 1 x 2.25 = 2.25; devices: 1 x 2 x 2.25 = 4.50; grounding conductors, ALL as one: 1 x 2.25 = 2.25. Total = 33.75 cu in. Up to four equipment grounding conductors together count as ONE volume allowance, and each device yoke counts as TWO.

Reference: NEC 314.16(B)

Problem 2. Per 314.16(B), what minimum box volume in cubic inches is required for a box containing 10 current-carrying 12 AWG conductors passing through, 2 equipment grounding conductors, 1 device mounted on a yoke (receptacle or switch)?

Answer: 29.25 cu in

Look up the volume 314.16(B) assigns to 12 AWG in your Code book, then add each item: conductors: 10 x 2.25 = 22.50; devices: 1 x 2 x 2.25 = 4.50; grounding conductors, ALL as one: 1 x 2.25 = 2.25. Total = 29.25 cu in. Up to four equipment grounding conductors together count as ONE volume allowance, and each device yoke counts as TWO.

Reference: NEC 314.16(B)

Problem 3. Per 314.16(B), what minimum box volume in cubic inches is required for a box containing 12 current-carrying 12 AWG conductors passing through, 2 equipment grounding conductors?

Answer: 29.25 cu in

Look up the volume 314.16(B) assigns to 12 AWG in your Code book, then add each item: conductors: 12 x 2.25 = 27.00; grounding conductors, ALL as one: 1 x 2.25 = 2.25. Total = 29.25 cu in. Up to four equipment grounding conductors together count as ONE volume allowance, and each device yoke counts as TWO.

Reference: NEC 314.16(B)

Practice against the clock

Train on the full simulator

Full-length timed exams at the real format, unlimited practice with new numbers every time, drills on your weak subject areas, and study material: a four-week plan, exam-day strategy and the mistakes to avoid in each subject area.

Get full access$19 per month. Cancel any time.
First month refunded within 7 days.

Common questions

How many volume allowances does a receptacle count for in box fill?

Two, based on the largest conductor connected to that device.

Do equipment grounding conductors count in box fill?

Yes, but together. Up to four equipment grounding conductors count as a single volume allowance based on the largest one.