Conduit fill calculations
Conduit fill compares two areas: the total cross-sectional area of the conductors, and the share of the raceway the Code lets you use. Chapter 9, Table 1 sets that share at 53% for one conductor, 31% for two, and 40% for more than two.
The method
- Look up the area of one conductor, for its size and insulation type, in Chapter 9, Table 5.
- Multiply by the number of conductors to get the area they occupy.
- Look up the total area of the raceway, for its type and trade size, in Chapter 9, Table 4.
- Apply the Table 1 percentage for the number of conductors to get the usable area.
- If the conductors need more than the usable area, go up one trade size and check again.
The common mistake is using 40% for one or two conductors. One conductor is allowed 53% and two are allowed only 31%.
Worked problems
Problem 1. Five 4 AWG THHN conductors are installed in 1-inch EMT. What total cross-sectional area do the conductors occupy?
Answer: 0.4865 sq in
Look up the area of one 4 AWG THHN in Table 5 and multiply by 5: 0.0973 x 5 = 0.4865 sq in. With 5 conductors, Table 1 permits 40% of the raceway area. 1-inch EMT has 0.866 sq in total, so 0.3464 sq in is usable. The conductors occupy 56.2%: it does NOT fit; go up one trade size.
Reference: NEC Chapter 9, Table 1 (fill percentages), Table 4 (EMT) and Table 5 (areas)
Problem 2. Twelve 6 AWG THHN conductors are installed in 1-1/4-inch EMT. What total cross-sectional area do the conductors occupy?
Answer: 0.8712 sq in
Look up the area of one 6 AWG THHN in Table 5 and multiply by 12: 0.0726 x 12 = 0.8712 sq in. With 12 conductors, Table 1 permits 40% of the raceway area. 1-1/4-inch EMT has 1.495 sq in total, so 0.5980 sq in is usable. The conductors occupy 58.3%: it does NOT fit; go up one trade size.
Reference: NEC Chapter 9, Table 1 (fill percentages), Table 4 (EMT) and Table 5 (areas)
Problem 3. Six 4 AWG THHN conductors are installed in 1-inch EMT. What total cross-sectional area do the conductors occupy?
Answer: 0.5838 sq in
Look up the area of one 4 AWG THHN in Table 5 and multiply by 6: 0.0973 x 6 = 0.5838 sq in. With 6 conductors, Table 1 permits 40% of the raceway area. 1-inch EMT has 0.866 sq in total, so 0.3464 sq in is usable. The conductors occupy 67.4%: it does NOT fit; go up one trade size.
Reference: NEC Chapter 9, Table 1 (fill percentages), Table 4 (EMT) and Table 5 (areas)
Practice against the clock
Train on the full simulator
Full-length timed exams at the real format, unlimited practice with new numbers every time, drills on your weak subject areas, and study material: a four-week plan, exam-day strategy and the mistakes to avoid in each subject area.
First month refunded within 7 days.
Common questions
What is the maximum conduit fill for more than two conductors?
40% of the cross-sectional area of the raceway, under Chapter 9, Table 1.
Why is the fill for two conductors lower than for three?
Chapter 9, Table 1 allows 31% for two conductors, 40% for more than two and 53% for one.